Construction
1. Conductor
Stranded bare copper wires
Class II according IEC 60228
2. Insulation
PVC
Identification: blue, black. Numbered.
3. Composition
Twisted pairs laid up together
4. Overall screen
Aluminium/polyester tape + flexible drain wire Cu-Sn
Overlap: 25%
Coverage: 100%
5. Inner sheath
PVC
Colour: Black or Blue (See table)
6. Armour
Galvanised steel wire armour
7. Outer sheath
PVC
Colour: Black or Blue (See table)
(*Other colours also available under order)
Technical characteristics
1. Operating voltage
300/500 V
2. Test Voltage
2000 V
3. Operating Tª
Service:-15°C to +70°C
Dureing installation: 0°C Min.
4. Insulation resistance
>10 MOhm x Km
5. Capacitance
250 pF/m Max.
6. L/R ratio
40 µH/Ohm
Standards / Properties
1. Ref. standard for drawing
According EN 50288-7
2. CPR Classification (Euroclass)
Eca
(According UNE-EN 50575)
3. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
4. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
5. Hydrocarbon resistant
UIC 895-OR