cable cerviflam h07zz f 450750v cpr

Cable with outer sheath and insulation of rubber mix with resistance to medium mechanical stress, weathering, humidity, oil, ozone and UV rays. Suitable for the wiring of lifting devices, machinery, etc. Of obligatory installation (according to the RBT-02 regulation) in ports and marinas for pleasure boats (ITC-BT 42), lifting and

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Cable Cerviflam H07ZZ-F 450/750V CPR
~\ImgCli\FOTO2_1015.jpg
Cable with outer sheath and insulation of rubber mix with resistance to medium mechanical stress, weathering, humidity, oil, ozone and UV rays. Suitable for the wiring of lifting devices, machinery, etc. Of obligatory installation (according to the RBT-02 regulation) in ports and marinas for pleasure boats (ITC-BT 42), lifting and transport machines (ITC-BT 33), provisional and temporary works (ITC-BT 34) and caravan connection devices (ITC-BT 41).
No propagador de la llama
No propagador incendio
Libre halogenos
Humos baja opacidad
Flexible
Baka corrosividad gases
Resistente UV
Technical characteristics
1. Operating voltage
450/750 V
2. Test Voltage
2500 V
3. Min. bending radius
Fixed installation:
3xD (Diameter <= 12 mm)
4xD (Diameter > 12 mm)
Free movement:
4xD (Diameter <= 12 mm)
6xD (Diameter >12 mm)
4. Operating Tª
Fixed service (protected installation): -40°C a +90°C (conductor)
During installation: -5°C a +70°C
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
Cross liked elastomer compound, rubber (Typo EI8)
Identification: See attached table
3. Assembly
Insulated conductors laid up together in concentric layers
4. Outer sheath
EPR rubber (Tipo EM8)
Standard colour: Black
Standards
1. CPR Classification (Euroclass)
Cca-s1b,d1,a1
(According to UNE-EN 50575)
Standards / Properties
1. Ref. for construction/drawing
UNE-EN 50525-3-21
2. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
3. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
4. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
5. Other characteristics
UV resistant
6. Low smoke emission
UNE-EN 61034 (IEC 61034)