Armoured cable Cerviflex ROVMV K 061 kV CPR

Armoured and shielded power and control cable for use in fixed installations, protected or not. Suitable for indoor and outdoor installations, on airborne supports, in pipes or buried. Thanks to its wire armour and the special PVC outer sheath, especially recommended where high mechanical or rodent protection is required and

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Armoured cable Cerviflex ROVMV-K 0,6/1 kV CPR
~\ImgCli\FOTO2_475.jpg
Armoured and shielded power and control cable for use in fixed installations, protected or not. Suitable for indoor and outdoor installations, on airborne supports, in pipes or buried. Thanks to its wire armour and the special PVC outer sheath, especially recommended where high mechanical or rodent protection is required and in contact with hydrocarbons and/or mineral oils.
Protegido electromagneticas
No propagador de la llama
No propagador incendio
Hidrocarburos
Anti roedores
Resistente aceites
Enterrado directo
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
XLPE Cross-linked polethylene
Identification: HD 308 (See table)
3. Assembly
Insulated conductors laid-up together in concentric layers
4. Overall screen
Polyester Tape + Aluminium/polyester tape + flexible tinned copper drain wire
Overlapp: 25%
Coverage: 100%
5. Inner sheath
PVC (Type ST2)
6. Armour
Galvanised steel wire armour
*In case of unipolar cables (ROVMAV-K), a aluminium wire armour is used (amagnetic)
7. Outer sheath
PVC RH (Type ST2)
Colour standard: Black (*Other colours under order)
Technical characteristics
1. Operating voltage
600/1000 V
2. Test Voltage
3500 V
3. Operating Tª (conductor)
Fixed installation: -15°C to +90°C
During installation: 0°C Minimum
Shortcut (Max. 5 seg): 250°C
4. Min. bending radius
10xD
Standards
1. Design
Special design according UNE 21123-2, IEC 60502-1
2. CPR Classification (Euroclass)
Eca (According UNE-EN 50575)
3. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
4. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
5. Hydrocarbon resistant
UIC 895-OR