shielded cable cervicord nycwy 061 kv cpr

Shielded cable by concentric conductor, designed for use in industrial processes in fixed installations with high levels of electromagnetic interferences, like power cable and control applications. Especially recommended for the connection of frequency inverters and motors.
Suitable for indoor and outdoor installations. The concentric conductor must be used as neutral, protective

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Shielded cable Cervicord NYCWY 0,6/1 kV CPR
~\ImgCli\FOTO2_480.jpg
Shielded cable by concentric conductor, designed for use in industrial processes in fixed installations with high levels of electromagnetic interferences, like power cable and control applications. Especially recommended for the connection of frequency inverters and motors.
Suitable for indoor and outdoor installations. The concentric conductor must be used as neutral, protective conductor or ground conductor. Simultaneously, it is also allowed to use it as a screen.
Protegido electromagneticas
No propagador de la llama
Flexible
Resistente UV
Construction
1. Conductor
MATERIAL:
Bare annealed copper
COMPOSITION:
· Cross-sectional areas until 16mm2: Circular rigid conductor (Class I)
· Cross-sectional of 25mm2 : Stranded (Class II)
· Cross-sectional areas until 240mm2: Stranded, sectorial shape (Class II)
2. Insulation
PVC (DIV4 Type)
Identification: Acc. to HD308 (See attached table)
3. Assembly
Insulated conductors laid up together
4. Inner sheath
PVC
5. Screen
Copper wires concentric conductor + conunter helix copper tape
*The cross-sectional area of the screen is specified in the cable composition, after the cross sectional area of the conductors, separated by: /
6. Outer sheath
PVC (DMV5 Type) UV Resistant
Colour: Black
Technical characteristics
1. Operating voltage
600/1000 V
2. Test Voltage
4000 V
3. Operating Tª (conductor)
Operating: -5°C +70°C
*Minimum conductor Tª (fixed service, permanent): -30°C
During installation: -5°C Mín.
Standards
1. Design
VDE 0276-603
2. Flame Retardant
VDE 0482-332-1-2 (IEC 60332-1)
3. CPR Classification (Euroclass)
Eca
(Acc. to UNE-EN 50575)
4. Other characteristics
UV Resistant