cable cervicom profibus dp armoured

Bus cable for data transmission systems (Profibus DP) in industrial processes in fixed outdoor installations. When an additional mechanical protection is required (directly buried).

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Cable Cervicom Profibus DP ARMOURED
~\ImgCli\FOTO2_1768.jpg
Bus cable for data transmission systems (Profibus DP) in industrial processes in fixed outdoor installations. When an additional mechanical protection is required (directly buried).
Profi bus
Anti roedores
Resistente UV
Enterrado directo
Technical characteristics
1. Operating voltage
30 V
2. Test Voltage
500 V
3. Min. bending radius
15xD
4. Insulation resistance
200 MOhm*Km Min.
5. Conductor resistance
60 Ohm/Km Max.
6. Operating Tª
-10°C +80°C
7. Transmission speed
12 Mbit/s (Max. 200m)
0,6 kbit/s (Max. 1000m)
8. Capacitance
30 pF/m
9. Impedance
150 Ohm
Construction
1. Conductor
Bare copper wire
Diameter: 1x0,64mm (AWG22)
2. Insulation
Polyolefin
Diameter: 2,5mm
Colours: Red, Green
3. Assembly
Two insulated conductors twisted together as a pair
4. Outer sheath
Polyethylene
Colour: Black
5. Inner sheath
PVC
Colour: Violet (RAL 4001)
6. Armour
Galvanized iron wire braid
Coverage: 80%
7. Screen
Aluminium/polyester tape
Coverage: 100%
+
Tinned copper wire braid
Coverage: 60%