cable cervicom bus eib knx cpr

For control of domotic systems in buildings. In accordance with the EIB (European Installation Bus) and KNX systems. Generally used to control lighting, blinds, heating, ventilation, indicator panels, etc....

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Cable Cervicom BUS EIB-KNX CPR
~\ImgCli\FOTO2_1062.jpg
For control of domotic systems in buildings. In accordance with the EIB (European Installation Bus) and KNX systems. Generally used to control lighting, blinds, heating, ventilation, indicator panels, etc....
Protegido electromagneticas
No propagador de la llama
Technical characteristics
1. Operating voltage
250V Max. A.C
300V Max. C.C
(*No apto para su conexión directa a la red de alimentación eléctrica o a otras fuentes de baja impedancia)
2. Test Voltage
1000 V
3. Insulation resistance
1000 MOhm*Km
4. Conductor resistance
36 Ohm/Km Max.
5. Characteristic Impedance
100 Ohm
6. Operating Tª
-15° to +70°C
7. Capacitance
50 ±10 pFm
Construction
1. Conductor
Bare copper wire 0,80mm
2. Insulation
Polyethylene ADPE
Identification:
· 1 pair: Red-Black
· 2 pairs: Red-Black + White-Yellow
3. Composition
1 pair: Two conductors insulated twisted together
2 pairs: Conductors laid-up in star (Star Quad)
4. Outer sheath
PVC (Type TM51)
Colour: Green
5. Screen
Polyester tape separator +
Aluminium/Polyster tape + tinned copper drain wire (0,51mm)
Standards
1. CPR Classification (Euroclass)
Eca
(According UNE-EN 50575)
Standards / Properties
1. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)