shielded cable cerviflam z1c4z1 k as 300500v cpr

Flexible shielded instrumentation and control cable for fixed installations in industrial processes or buildings. Especially recommended when good electromagnetic protection and good cable fire performance is required.

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Shielded cable Cerviflam Z1C4Z1-K (AS) 300/500V CPR
~\ImgCli\FOTO2_381.jpg
Flexible shielded instrumentation and control cable for fixed installations in industrial processes or buildings. Especially recommended when good electromagnetic protection and good cable fire performance is required.
Protegido electromagneticas
No propagador de la llama
No propagador incendio
Libre halogenos
Humos baja opacidad
Flexible
Baka corrosividad gases
Technical characteristics
1. Operating voltage
300/500 V
2. Test Voltage
2000V
3. Min. bending radius
8xD
4. Operating Tª
Fixed installation: -15°C to +70°C
During installation: 0°C Min.
Short-circuit (Max. 5 seg): 160°C
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
Halogen free compound
Identification: HD 308 S2 (See attached table)
3. Composition
Insulated conductors laid-up together in concentric layers
4. Outer sheath
Halogen free compound
Colour: Green
(Other colours under order)
5. Screen
Bare copper wire braid
Coverage: 60% aprox.
Standards
1. CPR Classification (Euroclass)
Cca-s1b,d1,a1
(According to UNE-EN 50575)
Standards / Properties
1. Ref. for construction/drawing
Special design, based on EN 50288-7
2. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
3. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
4. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
5. Low corrosivity
UNE-EN 60754-2 (IEC 60754-2)
(pH >= 4,3 ; conductivity =< 10µS/mm)
6. Low smoke emission
UNE-EN 61034 (IEC 61034)