shielded cable cerviflam vfd as 061kv

Shielded and halogen-free flexible cable designed for use in industrial processes and motors powe supply. In fixed installations where improved behavior against fire is required. Thanks to its double shielding and symmetrical distribution of the protective conductor, specially recommended for variable frequency drives.

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Cable apantallado Cerviflam VFD 0,6/1kV
~\ImgCli\FOTO2_1555.jpg
Shielded and halogen-free flexible cable designed for use in industrial processes and motors powe supply. In fixed installations where improved behavior against fire is required. Thanks to its double shielding and symmetrical distribution of the protective conductor, specially recommended for variable frequency drives.
Protegido electromagneticas
No propagador de la llama
No propagador incendio
Libre halogenos
Humos baja opacidad
Baka corrosividad gases
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
XLPE (Cross-linked polethylene)
Identification: See attached table
3. Assembly
· Up to 10mm2: Insulated conductors laid up together.
· From 16mm2: 3x + 3G configuration, the protection core Yellow/Green is divided in three cores which are placed in the interstices of the central conductors
4. Overall screen
Aluminium/polyester tape
+
Tinned copper wire braid (65%)
Total coverage:100%
*Eventually, separating tape over the braid (under the cover)
5. Outer sheath
Halogen free compound
Colour: Black
Technical characteristics
1. Operating voltage
0,6/1 kV
2. Test Voltage
3500 V
3. Operating Tª (conductor)
Service: -15°C a +90°C
Short-circuit: 250°C (5s Max.)
4. Min. bending radius
10 x D
Standards / Properties
1. Ref. standard for drawing
Based on IEC 60502-1
2. CPR Classification (Euroclass)
Eca
(According to UNE-EN 50575)
3. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
4. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
5. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
6. Low corrosivity
UNE-EN 60754-2 (IEC 60754-2)
(pH >= 4,3 ; conductividad =< 10µS/mm)
7. Low smoke emission
UNE-EN 61034 (IEC 61034)