cable cervicom profibus dp hf

Bus cable for data transmission systems (Profibus DP) in industrial processes in fixed installations. When cero halogen emission is required in case of fire.

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Cable Cervicom Profibus DP HF
~\ImgCli\FOTO2_1760.jpg
Bus cable for data transmission systems (Profibus DP) in industrial processes in fixed installations. When cero halogen emission is required in case of fire.
Protegido electromagneticas
Profi bus
No propagador de la llama
Libre halogenos
Construction
1. Conductor
Bare copper wire
Diameter: 1x0,64mm (AWG22)
2. Insulation
Foam polyolefin (Foam-Skin)
Diameter: 2,5mm
Colours: Red, Green
3. Assembly
Two insulated conductors twisted together as a pair
4. Screen
Aluminium/polyester tape
Coverage: 100%
+
Tinned copper wire braid
Coverage: 85%
5. Outer sheath
Halogen free compound
Colour: Violet (RAL 4001)
Technical characteristics
1. Operating voltage
30 V
2. Test Voltage
1000 V
3. Operating Tª
-20°C +80°C
4. Min. bending radius
5xD
5. Mutual capacitance
30 pF/m Max.
6. Characteristic Impedance
150 ± 15 Ohm
7. Transmission speed
12 Mbit/s (200m maximum length)
0,6 kbit/s (1000m maximum length)
8. Conductor resistance
60 Ohm/Km Max.
9. Insulation resistance
200 MOhm*Km Min.
Standards / Properties
1. Reference standards
UL File No: E83517
UL 80°C 30V - CSA AWM I/II A/B 80°C 30V
2. Flame Retardant
UL VW-1 - CSA FT1 - IEC 60332-1 - CEI 20-35