shielded cable cervipar par pos 300500v frlshf

Flexible instrumentation and control cable designed for use in industrial processes with high levels of electromagnetic interference. For fixed installations, recommended where an improved fire performance is required.

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Shielded Cable CERVIPAR PAR POS 300/500V FRLSHF
~\ImgCli\FOTO2_270.jpg
Flexible instrumentation and control cable designed for use in industrial processes with high levels of electromagnetic interference. For fixed installations, recommended where an improved fire performance is required.
Protegido electromagneticas
No propagador de la llama
No propagador incendio
Libre halogenos
Humos baja opacidad
Flexible
Baka corrosividad gases
Technical characteristics
1. Operating voltage
300/500 V
2. Test Voltage
1500V
3. Min. bending radius
8xD
4. Operating Tª (conductor)
Fixed installation: -15°C to +70°C
During installation: 0°C Minimum
Shortcut (Max. 5 seg): 160°C
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
Halogen free compound
Identification: Blue + Numbered Black
3. Assembly
Shielded pairs wired together
4. Composition
Two twisted insulated conductors forming a pair
5. Overall screen
Aluminium/Polyester tape + tinned copper drain wire
6. Individual screen
Aluminium/Polyester tape + tinned copper drain wire
7. Outer sheath
Halogen free compound
Usual color: Green
(*Other colours under order)
Standards / Properties
1. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
2. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
3. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
4. Low corrosivity
UNE-EN 60754-2 (IEC 60754-2)
(pH >= 4,3 ; conductivity =< 10µS/mm)
Standards
1. Design
According EN 50288-7
Standards / Properties
1. Low smoke emission
UNE-EN 61034 (IEC 61034)