screened cable cervipar par pos 500v cpr

Flexible instrumentation and control cable for transmission of analog or digital signals and control of industrial equipment. With individual screen on each pair in addition to the general one, especially suitable when protection against electrical noise is required.

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Screened Cable Cervipar PAR POS 300/500V CPR
~\ImgCli\FOTO2_197.jpg
Flexible instrumentation and control cable for transmission of analog or digital signals and control of industrial equipment. With individual screen on each pair in addition to the general one, especially suitable when protection against electrical noise is required.
Protegido electromagneticas
No propagador de la llama
Flexible
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
PVC (Polyvinyl chloride)
Identification: Blue + Black.
(At least one of the two conductors is numbered indicating the pair number)
3. Composition
Individually shielded twisted pairs laid up together
4. Individual screen
Aluminium/polyester tape + flexible tinned copper drain wire
Overlap: 25%
Coverage: 100%
5. Overall screen
Aluminium/polyester tape + flexible tinned copper drain wire
Overlap: 25%
Coverage: 100%
6. Outer sheath
PVC (Polyvinyl chloride)
Colour: Black
Technical characteristics
1. Operating voltage
300/500V
2. Test Voltage
2000V
3. Operating Tª (conductor)
Fixed installation: -15°C a +70°C
During installation: 0°C Mínimo
Short-circuit (Max. 5 seg): 160°C
4. Min. bending radius
8xD
5. Insulation resistance
10 MOhm*Km Min.
6. Mutual capacitance
<250 nF/Km
Standards
1. Ref. standard for drawing
Based on EN 50288-7
2. CPR Classification (Euroclass)
Eca
(According to standard UNE-EN 50575)
3. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)