shielded cable cerviflex rc4v k 300500v cpr

Flexible instrumentation and control cable for use in fixed installations. With copper wire braid screen, especially recommended for locations where good protection against electromagnetic interference is required.

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Shielded Cable Cerviflex RC4V-K 300/500V CPR
~\ImgCli\FOTO2_198.jpg
Flexible instrumentation and control cable for use in fixed installations. With copper wire braid screen, especially recommended for locations where good protection against electromagnetic interference is required.
Protegido electromagneticas
No propagador de la llama
Flexible
Construction
1. Conductor
Flexible bare copper wires
Class V according to UNE-EN 60228
2. Insulation
XLPE (Cross-linked polethylene)
Identification: HD 308 S2 (See colour table)
3. Composition
Insulated conductors laid up together
4. Screen
Bare copper wires braid
Coverage: 60%
5. Outer sheath
PVC (Polyvinyl chloride)
Colour: Black
Technical characteristics
1. Operating voltage
300/500 V
2. Test Voltage
2000 V
3. Operating Tª (conductor)
Fixed installation: -15°C to +90°C
During installation: 0°C Mín.
Short-circuit (Max. 5 seg): 250°C
4. Min. bending radius
8xD
Standards
1. Design
Based on EN 50288-7
2. CPR Classification (Euroclass)
Eca
(According to UNE-EN 50575)
3. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)