Cable Cerviflam Z1Z1 F AS 300500V

Flexible instrumentation and control cable with halogen free outer sheath suitable for mobile uses (ordinary services without load, not guided) in locations where a low level of smoke and corrosive gas emission in case of fire is required.

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Cable Cerviflam Z1Z1-F (AS) 300/500V
~\ImgCli\FOTO2_200.jpg
Flexible instrumentation and control cable with halogen free outer sheath suitable for mobile uses (ordinary services without load, not guided) in locations where a low level of smoke and corrosive gas emission in case of fire is required.
No propagador de la llama
Libre halogenos
Humos baja opacidad
Flexible
Baka corrosividad gases
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
Thermoplastic halogen free compound
Identification: HD 308 S2 (See attached table)
3. Composition
Insulated conductors laid up together
4. Outer sheath
Thermoplastic halogen free compound
Colour: Green
Technical characteristics
1. Operating voltage
300/500 V
2. Test Voltage
2000 V
3. Operating Tª (conductor)
Fixed installation: -15°C to +70°C
Short-circuit (Max. 5seg): +150°C
4. Min. bending radius
Fixed installation:
3xD (Diameter <=12 mm)
4xD (Diameter >12 mm)
Free movement:
5xD (Diameter <= 12 mm)
6xD (Diameter >12 mm)
Standards
1. Ref. for construction/drawing
Based on EN 50288-7
2. CPR Classification (Euroclass)
Eca (According to UNE-EN 50575)
*IMPORTANT NOTE: This information (CPR classification) must be confirmed in case of order against existing stock at that time.
3. Flame Retardant
UNE-EN 60332-3 (IEC 60332-3)
4. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
5. Low corrosivity
UNE-EN 60754-2 (IEC 60754-2)
(pH >= 4,3 ; conductivity =< 10µS/mm)
6. Low smoke emission
UNE-EN 61034 (IEC 61034)