cerviflam power cable rz1 k as 061 kv cpr

Flexible power cable for distribution of electrical energy in fixed installations. Suitable for indoor and outdoor installations, on air supports, in tubes or buried. Specially recommended for installations in public places (according to ITC-BT 28) and generally in all locations where an improved cable fire performance is required. In accordance

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Cerviflam Power Cable RZ1-K (AS) 0,6/1 kV CPR
~\ImgCli\FOTO2_179.jpg
Flexible power cable for distribution of electrical energy in fixed installations. Suitable for indoor and outdoor installations, on air supports, in tubes or buried. Specially recommended for installations in public places (according to ITC-BT 28) and generally in all locations where an improved cable fire performance is required. In accordance with the Low Voltage Regulation REBT 2002, specially for the following instructions (ITC-BT): 14, 15, 20, 28, 29 (Under metal tube).
No propagador de la llama
No propagador incendio
Libre halogenos
Humos baja opacidad
Flexible
Baka corrosividad gases
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
XLPE (Cross-linked polethylene)
Identification: HD 308 S2 (See colour table)
3. Composition
Insulated conductors laid up together
4. Bedding
Eventually (if necessary): Halogen-free thermoplastic compound, which can be integrated with the outer cover.
5. Outer sheath
Halogen free compound
Colour: Green
Technical characteristics
1. Operating voltage
600/1000 V
2. Test Voltage
3500 V
3. Operating Tª (conductor)
-15°C +90°C
4. Min. bending radius
5xD
Standards / Properties
1. Reference standards
UNE 21123-4, IEC 60502-1
2. CPR Classification (Euroclass)
Cca-s1b,d1,a1
(According to UNE-EN 50575)
3. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
4. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
5. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
6. Low corrosivity
UNE-EN 60754-2 (IEC 60754-2)
(pH >= 4,3 ; conductivity =< 10µS/mm)
7. Low smoke emission
UNE-EN 61034 (IEC 61034)