cable cerviflam h07zz f 450750v cpr

Cable with outer sheath and insulation of rubber mix with resistance to medium mechanical stress, weathering, humidity, oil, ozone and UV rays. Suitable for the wiring of lifting devices, machinery, etc. Of obligatory installation (according to the RBT-02 regulation) in ports and marinas for pleasure boats (ITC-BT 42), lifting and

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Cable Cerviflam H07ZZ-F 450/750V CPR
~\ImgCli\FOTO2_1015.jpg
Cable with outer sheath and insulation of rubber mix with resistance to medium mechanical stress, weathering, humidity, oil, ozone and UV rays. Suitable for the wiring of lifting devices, machinery, etc. Of obligatory installation (according to the RBT-02 regulation) in ports and marinas for pleasure boats (ITC-BT 42), lifting and transport machines (ITC-BT 33), provisional and temporary works (ITC-BT 34) and caravan connection devices (ITC-BT 41).
No propagador de la llama
No propagador incendio
Libre halogenos
Humos baja opacidad
Flexible
Baka corrosividad gases
Resistente UV
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
Cross liked elastomer compound, rubber (Typo EI8)
Identification: HD 308 S2 (see attached table)
3. Composition
Insulated conductors laid up together
4. Outer sheath
EPR rubber (Tipo EM8)
Colour: Black
Technical characteristics
1. Operating voltage
450/750 V
2. Test Voltage
2500 V
3. Operating Tª (conductor)
Fixed service (protected installation): -40°C to +90°C
Mobile service: -5°C to +70°C
4. Min. bending radius
Fixed installation:
3xD (Diameter <= 12 mm)
4xD (Diameter > 12 mm)
Free movement:
5xD (Diameter <= 12 mm)
6xD (Diameter >12 mm)
Standards / Properties
1. Reference standards
UNE-EN 50525-3-21
2. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
3. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
4. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
5. Low smoke emission
UNE-EN 61034 (IEC 61034)
6. Other characteristics
UV resistant
7. CPR Classification (Euroclass)
Cca-s1b,d1,a1
(According to UNE-EN 50575)