armoured cable cerviflam rz1mz1 k as 061kv rh cpr

Armoured cable for transport and distribution of electrical energy in fixed installations. Suitable for indoor and outdoor installations, on supports in the air (protected from UV rays), in tubes or directly buried (great mechanical protection and against rodents). Suitable for installations in public places and places with risk of fire

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Armoured cable Cerviflam RZ1MZ1-K (AS) 0,6/1kV RH CPR
~\ImgCli\FOTO2_2622.jpg
Armoured cable for transport and distribution of electrical energy in fixed installations. Suitable for indoor and outdoor installations, on supports in the air (protected from UV rays), in tubes or directly buried (great mechanical protection and against rodents). Suitable for installations in public places and places with risk of fire or explosion (ATEX Zones), and in general in all locations where a safe behavior of the cable against fire is required. Thanks to the special hydrocarbon resistant compound cover, especially recommended for installations in the Oil and Gas industry.
No propagador incendio
Libre halogenos
Humos baja opacidad
Hidrocarburos
Baka corrosividad gases
Anti roedores
Antideflagrantes
Enterrado directo
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
XLPE (Cross-linked polethylene)
Identification: HD 308 S2 (See colour table)
3. Composition
Insulated conductors laid up together
4. Inner sheath
Halogen free compound
Colour: Black
5. Armour
Galvanised steel wire armour
Coverage: 90%
6. Outer sheath
Special halogen free compound RH
Colour: Black
Technical characteristics
1. Operating voltage
600/1000 V
2. Test Voltage
3500 V
3. Operating Tª (conductor)
-5°C +90°C
4. Min. bending radius
10xD
Standards / Properties
1. Reference standards
Based on IEC 60502-1
2. CPR Classification (Euroclass)
Cca-s1b,d1,a1
(According to UNE-EN 50575)
3. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
4. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
5. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
6. Low corrosivity
UNE-EN 60754-2 (IEC 60754-2)
(pH >= 4,3 ; conductivity =< 10µS/mm)
7. Low smoke emission
UNE-EN 61034 (IEC 61034)
8. Hydrocarbon resistant
UIC 895 OR